Tuesday, March 28, 2017

Vacuum Circuit Breaker Technology



  • The continuing use of vacuum interrupter technology

  • 1. Breaker Overview
  • The structure of an outdoor vacuum circuit breaker (VCB)
    is shown in Fig.1. The three-phase ganged interrupter assembly
    is mounted in a self-contained breaker module
    containing the operating mechanism, auxiliary switch,
    mechanical linkage, and vacuum interrupter (VI)
    mounted in its own support insulator. The mechanical
    linkage and supporting framework are isolated from
    the high voltage interrupter by an insulated drive rod
    and the interrupter support insulators.
    • 2. Features of Vacuum Interrupters
    2.1 The Property of Vacuum
    The dielectric strength of a vacuum is superior to
    other dielectric mediums such as air and SF6 gas as
    shown in Fig. 2. Due to high dielectric strength of a
    vacuum environment, it is possible to reduce the arcing
    time of the interrupter as the dielectric capabilities of
    a vacuum can better withstand the generated transient
    recovery voltage (TRV). The net result of this is the the magnetic force generated by the current flow, this will
    cause the arc to be forced from the point of origin across the
    spiral petal to the outer diameter of the contact. Once the
    arc is on the outer edge of the contact, the magnetic force
    along the outer diameter will cause the arc to rotate around
    the outside diameter of the contact until it is extinguished.
    The AMF contact structure will generate an axial magnetic
    field caused by the current flow through the contacts which
    in turn will create a diffuse arc (low energy arc) over the
    entire contact area dispersing the arc energy over the contact
    surface area. The diameter of spiral contacts can be smaller
    than that of the AMF contact structure for the same fault
    current rating due to its ability to rapidly move and control
    the arc energy. In comparison the AMF contacts are superior
    for applications which require long arcing times and require
    a high number of full fault interruptions.minimum arcing time of a 15 kV vacuum circuit breaker
    is approximately 1 to 2 ms. The higher dielectric capability
    of the vacuum will yield a lower arc voltage and therefore
    reduce the amount of arc energy to be dissipated across the
    contacts in comparison with other interrupting mediums.
    This results in vacuum interrupters being able to break
    large fault currents with a short interrupting time and with
    minimal contact erosion. These properties allow vacuum
    interrupters to have a very compact design.

    • 2.2 Basic Structure of Vacuum Interrupters
    The basic structure of a vacuum interrupter is shown in
    Fig. 3. The main contacts are installed in a ceramic insulator
    in which high vacuum approximately 10-5 Pa is maintained.
    The movable terminal is connected to the breaker mechanism
    through an insulated drive rod which will open and
    close the interrupter contacts. A stainless steel bellows is
    used to allow contact travel and still maintain the integrity of
    the vacuum in the interrupter. The contact material strongly
    affects the interrupting capability, service life, and reliability
    of the vacuum interrupter. There are three types of contact
    designs used in vacuum interrupters, and they are applied
    based on their application as shown in Table 1. Generally,
    in applications with fault currents below approximately 20
    kA, a flat butt type of contact design is sufficient. In applications
    where fault currents can exceed 20 kA, the design
    limitation of the contact will manifest itself as a localized
    high energy arc which results in large amounts of metal
    vapor being placed in the contact zone and thereby limiting
    the fault rating of the interrupter. In order to improve the
    interrupter’s fault capacity either the spiral or axial magnetic
    field (AMF) contact design can be applied. These contacts
    are used in higher fault ratings as they are able to utilize the
    force created by the magnetic fields associated with the fault
    current. This enables the interrupter to effectively control
    the generated arc and therefore create a more efficient interrupter
    design. The spiral contacts will generate a magnetic
    field caused by the current flow through the contact. Due to
    • 2.3 Arc Control During Interruption
    By using a high-speed video camera and a specially
    adapted vacuum chamber, the motion of the arc movement
    can be observed. Fig. 4 shows the movement of the
    arc for a spiral contact configuration during fault current
    interruption. At contact part plus 1.5 ms, the arc has been
    established between the contacts. At contact part plus 2 ms
    the arc is beginning to rotate around the outer edge of the
    contacts as a result of the magnetic forces that are being
    generated from the flow of the fault current through the
    contacts. This movement of the arc around the outer diameter
    of the contact surface provides the greatest amount of
    surface for the arc to travel over thus providing a larger area
    to distribute the heat generated from the arc. The net result
    of this movement of the arc is less localized overheating of
    the contact surfaces and therefore less metal vapor being
    introduced into the area between the contact surfaces. This
    greatly improves the interrupting capability of the interrupter
    and also results in less erosion of the contact surfaces,
    improving the life of the interrupter.
    Fig. 5 shows the arcing that takes place in an AMF
    contact configuration during fault interruption. At contact
    part plus 1 ms, the arc is beginning to be dispersed as a
    result of the axial magnetic fields generated by the contact
    geometry. This dispersal will generate numerous low energy
    arcs (macroscopically one diffused arc) which will spread
    out across the entire contact surface by contact part plus 3
    ms. As the contacts continue to separate, the density of the
    diffuse arc will continue to decrease so that at contact part
    plus 5 ms interruption will occur when the next current zero
    is encountered. By dispersing the arc energy into numerous
    low energy arcs spread across the entire contact surface,
    the amount of contact erosion and thus metal vapor in the
    contact area can be controlled. This will result in greater
    interrupting ratings for the contacts and longer contact life.
    • 2.4 Short Circuit Fault Interruption
    Fig. 6 shows a typical oscillograph during short-circuit
    current interruption. When the contacts separate during
    fault interruption an arc appears between the contacts and
    is maintained until the next current zero crossing is encountered.
    At the same time, an arc voltage is present across the
    contacts. Once the current flow is interrupted a TRV will
    appear across the contacts. If at the time the TRV appears,
    the dielectric withstand of the contact gap is greater than the
    TRV value, the current will be successfully interrupted. If the
    TRV is greater than the dielectric withstand of the contact
    gap, the arc will reappear and will be successfully interrupted
    at the next current zero crossing. This condition will occur
    when the time to the first zero crossing event is less than
    the designed minimum arcing time of the interrupter.
    • 3. Design Test
    The capability of a medium-voltage circuit breaker is
    verified by design tests specified in the IEEE/ANSI standards,
    C37 series. In the design tests, a series of capabilities
    (dielectric, current carrying, short-circuit current interruption,
    and other current switching) are tested to meet the
    required ratings. The following items, based on the design
    test requirements, need to be taken into consideration
    when demonstrating the circuit breaker’s capability and
    application.
    • 3.1 Asymmetrical Short-Circuit Current
    Interruption and the Effect of Various X/R
    Ratios
    3.1.1 The rated interrupting time of a circuit breaker is
    defined as the maximum permissible time interval
    between the energization of the trip circuit (at rated
    control voltage), and the interruption of the current
    in the main circuit in all three phases. The standards
    allow for ½ cycle of relay time prior to the trip circuit
    energizing. This ½ cycle of relaying time is not
    allowed to be counted as part of the interrupting
    time of the circuit breaker. A circuit breaker rated
    for three cycles must completely interrupt all current
    flowing in the main circuit by the time three cycles
    of 60 Hz current has passed (50 ms) after the trip
    circuit is energized. If the current continues to flow
    beyond the 50 ms, the breaker cannot be rated as a
    three-cycle breaker. A five-cycle breaker is one that
    interrupts the current between three and five cycles
    (50-83 ms) after the trip circuit is energized. If there
    is any current flow after 83 ms, the breaker cannot be
    rated as a five-cycle breaker. The interrupter must be
    able to interrupt current flow on the first or second
    current zero after contact part. See Fig. 7.
    • 3.1.2. A typical short-circuit asymmetrical wave is shown in
    Fig. 8. For a three-cycle circuit breaker, it is necessary
    to complete the interruption where the interrupting
    time is equal to or less than three cycles. Moreover,
    the test procedure in the IEEE standards requires
    demonstrating that an interrupter can reliably
    interrupt current under the most severe switching
    conditions with the maximum arcing energy (longest
    arcing time and a major loop of asymmetrical current).
    Symmetrical interruptions must be performed
    to meet the ANSI/IEEE standards. The test duties
    included in Table 1 of IEEE C37.09-1999 demonstrate
    the interrupter’s capability to interrupt current
    flow, both symmetrical and asymmetrical.
    • 3.1.3 The current peak value and major loop duration
    are controlled by the value of X/R. The X/R ratio
    is the ratio of the main circuit’s inductance divided
    by the resistance. The higher the ratio is, the slower
    the decay of the dc component of the asymmetrical
    fault current. Fig. 8 shows the decay characteristic
    of an asymmetrical current. Notice the peak current
    decreasing with time. A standard value of X/R is
    given as 17 at 60 Hz in IEEE Std C37.09-1999.
    However, the purchaser of the breaker needs to evaluate
    his system and verify that the X/R of the system
    is less than 17. When the circuit has an inherently
    high X/R, the interrupting time must still meet
    the interruption rating of the breaker (three or five
    cycles); however, the arcing time will increase due to
    a larger major current loop. The major loops will not
    only have an increased time between current zeros, it
    will also have a higher peak current due to a higher
    X/R ratio. Very high X/R ratios may not even have
    a current zero for the first couple of cycles. For example,
    if you compared an X/R=30 with an X/R=17
    (see Fig. 8), the arcing time increases by a factor of
    1.1, and the current peak value increases by a factor
    of 1.4.
    • 3.1.4 Symmetrical current interruptions must also be performed
    according to IEEE C37.09-1999, Table 1.
    The symmetrical interruptions are required for design
    testing and to verify that the contact serviceability
    as stated in IEEE C37.04-1999 section 5.8.2.5 is
    achieved. The standards require a minimum of 800
    percent of the required asymmetrical interrupting
    capability of the circuit breaker be accumulated on
    a single interrupter. Contact serviceability is the
    amount of contact erosion that the interrupter must
    be able to withstand and still be able to perform a
    successful interruption.
    1. 3.1.5 There are several design features that cause a vacuum
    interrupter to be superior to other types of interrupters
    for this application. The AMF style of contact
    inside the interrupter allows for a longer arcing time
    due to the low current density of the diffused arc. This
    reduced energy will keep the surface of the contacts
    from overheating and thus reduce the possibility of
    restrikes. The reduction of restrikes is due to reduced
    hot spots and reduced metal vapor in the contact gap. For circuit breakers rated below 100 kV, in IEEE Std
    C37.04-1999, the rated TRV is represented by a 1-cosine
    wave, while on the other hand, in IEC 62271-100, 2003
    the TRV is represented by an exponential-cosine wave as
    shown in Table 2 and Fig. 9. These ratings are for shortcircuit
    tests, duty 4 and duty 5 in IEEE C37.09 and for
    terminal fault test, duty T100a, in IEC. It is worth noting
    that in the IEEE standards the TRV specifications are
    different for outdoor and indoor applications. The outdoor
    specification is more severe than the indoor. Breakers tested
    and rated for indoor use, may not be suitable for outdoor
    applications. Also, the differences between the IEC and
    the IEEE TRV requirements are significant enough that
    breakers tested to the IEC standard may not pass testing
    for IEEE. The steeper slope of the recovery voltage will
    change the requirements of the contact design to achieve a
    greater rate of dielectric recovery inside the interrupter. The
    capability of the interrupter to successfully interrupt this
    high rate of rise of recovery voltages (RRRV) is dependent
    upon the internal geometry of the interrupter. The type of
    contact and the surrounding dielectric fields produced by
    the internal shield all have a large impact on the capability
    of the interrupter. The AMF style of contact is well suited
    for this purpose due to reduced hot spots and metal vapor
    in the contact gap. The smooth contact surface allows for
    a very rapid dielectric recovery of the gap which allows
    the vacuum interrupter to withstand the TRV better than
    other types of medium. The rapid recovery allows for small
    contact gaps, which translates to a very short stroke of the
    interrupter and operating mechanisms.
    • 3.3 Continuous Current Carrying Capability of
    Vacuum Interrupters
    3.3.1 The rated continuous current of a breaker is determined
    by the current carrying capability without
    exceeding the temperature limitations as listed in
    Table 2 of IEEE C37.04-1999. This temperature
    limit takes into consideration the types of materials,
    plating, and atmosphere that surround the point
    where the temperature is being measured.The TRV characteristics depend on the system in which a
    circuit breaker is installed. The TRV is controlled mainly by
    the amount of inductance and/or capacitance on each side
    of the breaker. However, to provide a general application
    guide, the TRV values under most system circuit conditions
    are specified in the following standards. The most common spot in a VCB where temperature
    rise is a concern is the moving stem of the vacuum
    interrupter. It is necessary to monitor the temperature
    very closely at this critical connection point where the
    current path must allow for the motion of conductors.
    A typical temperature rise graph is shown in Fig. 10.
    In a medium-voltage VCB, the thermal time constant
    is usually small. If a VCB is required to carry overload
    current for several hours, the temperature rise on a
    VCB will approach the saturation values. This temperature
    may be over the thermal limits of materials.
    Whether or not the breaker will exceed any critical
    temperature limits will need to be evaluated carefully.
    The IEEE standards cover standard overload
    requirements; refer to IEEE C37.10-1999 section
    5.4.4. If the breaker will be required to exceed these
    limits, the purchaser and manufacturer will need to
    review the continuous current test data to verify the
    breaker’s capability for higher overload ratings.temperature rise associated with the
    higher resistance. The spiral or butt
    type contact is generally better suited
    for high continuous currents than the
    AMF style of contact. Consideration
    must also be given to the location
    where the circuit breaker will be installed.
    If the installation site has an
    ambient temperature rating of 50°C,
    as compared to the 40°C used in
    the IEEE standards, then the total
    temperature rise must be decreased accordingly (by
    10°C in this case). The overall performance of the
    interrupter needs to be considered to determine the
    best contact design, material, and size for any given
    application. To ensure proper application of the circuit
    breaker, the purchaser and manufacturer should
    review the test reports.
    • 3.4 Dielectric Capabilities of Vacuum
    Interrupters.
    3.4.1 Vacuum interrupters are well suited to withstand
    voltage surges due to the rapid recovery of the dielectric
    strength of the contact gap caused by the high
    level vacuum. Other types of interrupter medium
    take much longer to recover due to the need to remove
    hot gas (in SF6 for example) from the gap. The
    smooth contact surfaces and surrounding geometry
    (primarily the internal shield), as well as the high
    level of vacuum, all contribute to the interrupter’s
    voltage withstand capability.
    3.4.2 Lightning Impulse Withstand Voltage (BIL)
    Vacuum is very reliable during lightning impulse
    withstand voltage. This is demonstrated by testing
    performed per section 4.4. of IEEE C37.09-1999.
    The flat design of contacts and the voltage profiling
    of the surrounding components (for example,
    the internal shield, bellows, moving contact stem,
    etc.) make this a very impulse friendly interrupter.
    Another factor that allows the small contact gap to
    withstand voltage surges is the high level of vacuum
    inside the interrupter. A high level vacuum eliminates
    all foreign particles within the interrupter. This results
    in having no impurities and a very low molecular
    count across the contact gap. The absence of foreign
    particles and molecules will not allow the voltage to
    jump across the internal gap.
    There are several ways of improving the external
    dielectric capabilities of a vacuum interrupter. Many
    manufacturers will use various types of minor modifications
    to improve the dielectric capabilities, or
    margins, within a particular interrupter design. Some
    examples are the use of an externally contoured, or
    shedded, porcelain body to increase the creepage
    distance. The increase in creepage distance allows for
    more margin in a high contamination environment 3.3.2 The size and design of the main contacts and conductors
    contribute to the continuous current rating
    of the interrupter. The larger the contact diameter,
    the better the current carrying capability. The contact
    design and material also play a part in the continuous
    current rating. The different contact materials may
    have different resistance values. A higher resistance
    value may limit the amount of current due to the
    Another example would be to use a heat shrink material
    on the ends to increase creep and strike. The use
    a potting material to completely cover the outside of
    the interrupter to increase the dielectric strength has
    also been used for increased margins or capabilities
    of a given interrupter design.
    Vacuum interrupters are ideal for use in low-, medium-,
    and even the lower end of high-voltage applications. Vacuum
    will eventually be used in high-voltage applications
    as technology keeps improving the capability of vacuum
    interrupters. The internal design of the vacuum interrupter,
    especially the main contacts, greatly impacts the capability of
    the interrupter. There are different types of contact designs
    that will utilize different materials to achieve different ratings
    and capabilities. The internal design of the interrupter
    will depend on the rating of the circuit breaker where the
    interrupter will be installed. Some of the items to consider
    on the internal design are not only the contact shape but also
    the internal shield shape, the moving stem shape, blending
    radii, and even the mounting configuration of the vacuum
    interrupter. Whether the breaker will be primarily used for
    capacitor switching duty, transformer magnetizing, or just
    fault interruptions, will affect the design. It is the responsibility
    of the end user of the circuit breaker to verify that
    the breaker (ultimately the interrupter) is suited to meet the
    specific needs of the system. The ability of the circuit breaker
    to function properly on a given system will ultimately come
    down to the review of the test data to ensure that the breaker
    has been tested and verified to function correctly under the
    duties in which it will be asked to perform.



    in the power distribution market as replacements
    for oil circuit breakers has exposed this technology
    to people who have not been previously exposed to it. This
    article covers the features of the vacuum interrupter and how
    they correspond to the ability of the interrupter to perform
    according to its ratings.
    Vacuum interruption technology has been used for
    many years and has proven itself to be a reliable means for
    interrupting fault currents in distribution switchgear. The
    application of vacuum circuit breakers as replacements for
    oil circuit breakers offers many advantages to the user in
    areas such as maintenance, performance, and environmental
    concerns. From a maintenance point of view, with a vacuum
    breaker there is no oil handling required with the associated
    clean up as well as long contact life and lower mechanism
    operating forces due to the small size and stroke required
    by a vacuum interrupter. A typical vacuum interrupter as
    applied in a distribution breaker will easily handle 10,000
    operations at rated continuous current and more than 20 full
    fault operations without the need for contact replacement.
    Also, as a result of the lower mechanical requirements the
    mechanisms in today’s vacuum breakers are much simpler
    in design with fewer moving parts and lighter loads being
    applied.



    No comments:

    Post a Comment